Skip to content
We create solutions that build better communities
Morrison-Maierle
Engineers Surveyors Planners and Scientists Morrison-Maierle
Primary Navigation Menu
Menu
  • What We Do
    • Airports
    • Buildings
    • Development
    • Industrial
    • Natural Resources
    • Survey
    • Transportation
    • Water-Wastewater
    • Morrison-Maierle Systems
  • Who We Are
    • About Us
      • Board of Directors
      • Corporate Leadership Team
      • Employee Ownership
      • Core Values
    • Blog
    • Webinars
    • Whitepapers
    • Press Room
      • Annual Reports
      • Awards & Honors
        • Firm Awards & Rankings
      • Employee-Owner News
      • In the Media
      • Press Releases
  • Where We Work
    • Locations
      • Bend
      • Billings
      • Bozeman
      • Casper
      • Cody
      • Gillette
      • Great Falls
      • Helena
      • Kalispell
      • Missoula
      • Sheridan
      • Spokane
  • Careers
  • Contact Us
    • Projects Bidding
VFD cabling

VFD Cable Selection and Grounding Considerations for Large Industrial Motors

Selecting the Right Cabling for Your Project

By Brian Literski, PE – Variable Frequency Drives (VFDs) are essential components that control the speed of process equipment. They are used with pumps, blowers, or other motor-driven equipment required to run at variable speeds or loads.
For some industrial projects that use process equipment, a motor’s horsepower requirements can be up to hundreds of horsepower on a 480V power distribution system. Since VFD output cabling provides the connection from the VFD to the process equipment motor, it is good practice to choose a cable that enhances the system’s performance. Selecting the right VFD cable for your project can alleviate some of the common issues VFDs can create.

Why VFD Cable vs. Building Wire?

Using building wire, like THHN/THWN, creates a risk for insulation failure caused by the high voltage spikes (greater than 600V) and the corona discharge responsible for damaging the jacket and/or insulation that a VFD can produce on conductors between the VFD and the motor. The standard THHN/THWN wire used on building electrical systems is rated only for use with 600V applications and is more susceptible to insulation breakdown on the output of a VFD.
On the other hand, VFD cable rated up to 1000V or 2000V (depending on the type specified) includes higher-grade insulation with three symmetrical grounds. This type of cable offers the proper shielding needed to reduce EMI/RFI noise by providing a low-impedance signal return path that prevents common-mode or stray voltage. The insulation rating on VFD cable is rated above the VFD output voltage spikes which are normally 1.7 times or more of the system voltage of 480V, so roughly 831V. The insulation in VFD cable is not strained like 600V rated THHN/THWN as it is rated above the voltage spikes. VFD cable protects against premature cable failure.

Bad Vibrations and VFDs: How to Mitigate Premature Motor Damage

Code Issues Using VFD Cable on Large Motors

If process equipment gets into the hundreds of horsepower, multiple parallel cables are required to meet the ampacity requirement of the motor’s full load current. When running multiple paralleled conductors, the equipment ground needs to be upsized to provide an adequate return path should a fault occur. The issue with VFD cable ground conductors on large equipment is with the cross-sectional area of the three-symmetrical grounding conductors; because they won’t meet the National Electric Code (NEC) requirements when placed in a parallel configuration (see NEC Table 250.122). The three-symmetrical ground conductors are fixed sizes based on the phase conductors.
Fortunately, two methods can correct this issue:

  1. Method 1 includes upsizing the phase conductors until the ground conductor size is adequate in the VFD cable.
  2. Method 2 includes using properly sized VFD cabling for the phase conductors and installing an additional equipment ground conductor as required in NEC 250.122 (F). 

With Method 1, the cost of upsizing the phase conductors in a cable can become so large that economic and installation issues make it less favorable or non-feasible. Method 2, on the other hand, includes an extra equipment ground wire in all the parallel conduit runs—and is allowed as per NEC 250.122 (F). Method 2 is by far the preferred approach because the cost of including only one extra equipment ground conductor per paralleled conduit (sized according to Table 250.122) is much more economical than upsizing three-phase conductors to meet the minimum equipment grounding cross-sectional area requirement.

Figure 1 – VFD Cable courtesy of the BELDEN Variable Frequency Drive Solutions brochure.

The cross-sectional area of the grounding conductors in Figure 1—when run in parallel to large motors —does not satisfy the NEC Table 250.122 requirements. An additional properly sized equipment grounding conductor (run with each VFD cable in parallel conduits) is required to fulfill NEC’s installation methods.

Next Steps

NEC requirements, like this example of equipment grounding conductor sizing, need to be followed to provide a safe, code-compliant industrial electrical system. Since all electrical distribution system requirements can vary depending on the project, it’s best to look at each project on a case-by-case basis. I’m always available to discuss your project’s system needs. Call or email me if you have questions about your system needs or designs.

Brian Literski

Brian Literski is a professional engineer who works in Morrison-Maierles’s Helena office. He provides electrical design engineering focusing on industrial power and control systems. Brian lives with his wife and three kids and especially enjoys skiing, mountain biking, and kiteboarding.

 

 

Related Articles

  • Bad Vibrations and VFDs: How to Mitigate Premature Motor Damage
  • The Basics of Switchboards, Switchgear, and Panelboards
  • Why is My Generator So Oversized?
  • Power Distribution in Your Building: Fulfilling Its Electrical Potential
  • Fire Protection Measures for Wastewater and Collection Facilities
2022-06-27
Previous Post: Celebrating International Women in Engineering Day
Next Post: Seeley Building

What We Do

Need assistance with engineering, planning, surveying, or science? To get a better idea of our services, explore our projects and experience.

Build Your Career

From entry- to senior-level positions in engineering, science, survey, and planning, we have career opportunities in Montana, Wyoming, Washington, and Oregon.

Contact Us

Questions? Inquiries? Let's talk!

Connect With Us

Morrison-Maierle has 12 offices in Montana, Wyoming, Oregon, and Washington.

Morrison-Maierle office locations

Montana | Kalispell, Missoula, Helena, Great Falls, Bozeman, Billings

Wyoming | Cody, Sheridan, Casper, Gillette

Oregon | Bend

Washington | Spokane

Morrison-Maierle Inc

Careers

If you thrive on work that has a broader purpose, you’ve come to the right place. View our jobs.

Get in Touch

Need to know more? Let’s start our conversation today. Contact us.

Social Media

Copyright© 2023 Morrison-Maierle | Montana • Wyoming • Oregon • Washington