What You Need to Know About Emergency Egress Lighting
By Ryan Maroney, PE
There is often much confusion regarding emergency egress lighting requirements for buildings. What is emergency egress lighting? Where is it required? How can we address these code requirements with aesthetic, cost-effective, and low-maintenance solutions? To help answer these questions, let’s start with some definitions and then dig in further.
Egress lighting illuminates the travel path from any occupied structure space out to a public way. Emergency egress lighting is similar, except that it must remain on during a loss of normal utility power. Various codes outline both requirements, but the latter often requires the most thought and planning, so let’s focus on that part for now.
What Does the Code Say?
The two most widely enforced codes in our region on emergency egress lighting requirements are the Life Safety Code (NFPA 101) and the International Building Code (IBC). Further reading can be found specifically in NFPA 101 Section 7.9, and IBC Section 1008.3, but in summary, these codes require the following:
Emergency illumination shall be provided for a minimum of 1½ hours in the event of failure of normal lighting. Emergency lighting facilities shall be arranged to provide initial illumination that is not less than an average of 1 footcandle and, at any point, not less than 0.1 footcandle, measured along the path of egress at floor level. (NFPA 101 7.9.2)
These performance requirements apply to all egress paths defined by IBC 1008.3. This includes interior spaces like vestibules, corridors, passageways, and exit stairways. However, it also includes exterior areas such as exterior landings at exit doorways and outdoor exit ramps and stairways. These exterior requirements are often overlooked and can be costly at the end of a project. It is important to coordinate with your architecture team on all exit paths and plan for interior and exterior emergency egress lighting early in design to avoid picking up these code requirements late in the game.
What Construction Types Fall Under These Requirements?
There are some limited exceptions, but all buildings other than basic residential dwelling units must generally follow these egress lighting code requirements. This includes new construction projects and renovation projects where existing building parts are being upgraded. In addition, in cases where public safety is a concern as determined by the Authority Having Jurisdiction (AHJ), some existing buildings must be retrofitted to conform with current egress lighting code requirements. It is important to check the aforementioned code sections and confirm with the local AHJ before assuming emergency egress lighting will not be required on a project.
Explore Solutions for Emergency Egress LightingWhy the Requirement in the First Place?
When the power goes out, whether from a utility outage, a fire event, or something else, a means must be in place to provide illumination so the building will not go pitch dark. This is especially important during a fire, where exit pathways need to remain lit to aid in getting people safely out of the building. Think about being in an unfamiliar building, possibly alone, when suddenly the fire alarm rings and the power goes out. You are going to want to get out of there immediately. Having some illumination will not only physically help you get out but also reduce panic and stress levels. The most important thing to remember is the goal of illuminating the path(s) needed to get people safely out and away from the building.
How Can We Address These Requirements?
There are some options when looking for ways to tackle emergency egress lighting, such as:
- Using standalone “bug-eye” light fixtures.
- Installing light fixtures with an internal battery backup.
- Provide a lighting inverter to back up select light fixtures upon normal power failure.
- Use a generator to provide backup power to select light fixtures upon normal power failure.